DIRECT SUPPORT MAINTENANCE
ADVANCED DESIGN REFRIGERATOR, 300 CUBIC FOOT (ADR-300)
REFRIGERATION UNIT DEHYDRATOR
REMOVE/INSTALL
INITIAL SETUP
Personnel Required
Tools and special tools
HVAC Technician (MOS 52C, AFSC 3E1x1) (1)
Tool Kit, Refrigeration Service
(WP 0051 00, Table 2, Item 5)
References
Refrigeration System Service (WP 0031 00)
Materials and Parts
Refrigerant R404A (WP 0068 00, Item 16)
Equipment Conditions
Compressor Oil (WP 0068 00, Item 5)
ADR-300 disconnected from all power sources.
NOTE
The following procedures involve servicing the refrigeration system.
Some of these service procedures are regulated by Federal, and in some
cases, by State and Local laws. All regulated refrigeration service
procedures must be performed by an EPA certified technician, using
approved equipment and complying with all Federal, State, and Local
laws.
NOTE
Replace the dehydrator whenever the high side is opened or when the
low side is opened for an extended period of time.
REMOVE
1. Remove the condenser section and top grille.
2. Complete the low-side pump down procedure outlined in WP 0031 00.
3. Remove the clamp around the dehydrator.
NOTE
Observe direction of refrigerant flow.
4. Disconnect the nuts at each end of the dehydrator, using a back-up wrench, and remove the
dehydrator from the clamp.
0037 00-1