TM  10-4130-239-14 5-28. START-RUN VALVE ASSEMBLY REPLACEMENT  (CONT) 4. Remove oil drain hose clamp. Move oil drain hose out of way. 5. Drive out handle pin. WARNING Polyurethane foam is flammable. Burning foam causes toxic fumes. When soldering, be very careful not to ignite foam. NOTE Desolder fittings as needed to remove from valve assembly. 6. Debraze START-RUN valve assembly (para 5-5). 7. Remove spacer. 8. Remove three fittings from valve assembly. 1. Install three fittings in valve assembly. 2. Install spacer. 5-68