Evaporator   Fan   Motor   Runs-Condenser   Fan   Motor   and   Compressor   Motor   will   not   Run (Selector Switch on COOL)
Up
TM-5-4120-259-15 Air Conditioner Horizontal Compact 9 000 BTU Trane Models Manual
Next
figure 10. daily preventive maintenance services
TM   5-4120-259-15 44.   Faulty   Blower Probable Cause Unbalanced   or   corroded   fans. Defective   fan   motor. 45.   Faulty   Receiver Probable Cause Receiver   develops   leaks. Relief      valve   defective. 46.  Suction  Pressure  Below  Normal Probable Cause Restricted   liquid   line   or   expansion   valve. Insufficient   refrigerant   charge. 47.  Suction  Pressure  too  High Probable Cause Overfeeding   of   expansion   valve. 48.   Defective   Motor   Contactor Probable Cause Circuit    breaker    defective. Holding   coil   defective. 49.  Dampers  Fail Probable Cause Damper   control   cable   defective. Control   linkage   binder   defective. Damper   blades   binding   in   frame. Possible  Remedy Replace   (para   57   and   58). Replace  motor  (para  57  and  58). Possible  Remedy Repair   leaks   or   replace   receiver   (fig.   31). Replace   valve   (fig.   31). Possible  Remedy Pump   down,   examine,   and   correct.   Replace   expansion valve   if   necessary   (para   84). Check   for   refrigerant   shortage.   Recharge   if   necessary (para   97). Possible  Remedy Regulate   expansion   valve,   and   check   bulb   attachment. Replace   if   necessary   (para   84). Possible Remedy Replace   circuit   breaker   (para   62). Replace   Motor   Contactor   (para   63). Possible  Remedy Replace  cable  (para  54). Check   damper   control   linkage.   Repair   or   replace as  needed. Free  blades  or  replace  (para  53). 16