Cleaning and Inspection - TM-5-4120-282-130070
Up
TM-5-4120-282-13 Air Conditioner Floor Mounted Aie Cooled Electric Motor Driven 3/4 HP 60 Cycle AC Single Phase 9000 BTU/HR Manual
Next
Cleaning and Inspection. - TM-5-4120-282-130072
(2) Inspect the receiver for leaks or damage.
(3) Replace a defective receiver.
Installation.
c.
(1) Install the receiver in the unit securing with hex nut under
the unit.
(2) Connect inlet and outlet tubes (para 75).
(3) Leak test, evacuate, and charge the system (para 74).
(4) Install top, left -side, and rear panels (para 39).
80. Strainer Dehydrator (figure 4).
a. Removal.
(1) Remove the top and right-side panels (para 39).
(2) Release refrigerant charge (para 74).
(3) Disconnect the inlet and outlet tubes from the strainer (para
(4) Remove the strainer (figure 4).
b.
Cleaning and Inspection. Throw away the strainer and replace.
c. Installation.
(1) Place the dryer strainer in the unit and connect the tubes
(para 75).
(2) Leak test, evacuate, and charge the refrigerant system (para
(3) Install top and right-side panels (para 39).
Expansion Valve
a. Removal.
(1) Remove the top and right-side panels (para 39).
(2) Release the refrigerant charge (para 74).
(3) Disconnect the flare inlet and outlet connections. Use only
a flare nut wrench (figure 4).