Click here to make tpub.com your Home Page

Page Title: Section II. MOVEMENT TO A NEW WORKSITE
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

Section II. MOVEMENT TO A NEW WORKSITE
2-4. Dismantling for Movement.
c.
Long
Distance
Movement.
Crate
the
air
conditioner,  providing  adequate  protection  to
a. General.
grilles and control panel. Refer to TM 38-250 for
(1) Shut off electrical power supply to air
i n s t r u c t i o n s in crate fabrication, if original shipping
conditioner and disconnect power cable from unit.
c r a t e is not available. Provide suitable blocking and
(2) Disconnect drain hose(s) from unit.
tie-downs to prevent unit from shifting during
NOTE
transfer and to keep the unit vertical.
Disconnect all duct work and remote control cable if
used with unit..
2-5. Reinstallation after Movement
Reinstall the air conditioner as instructed in
(3) Unbolt unit from mounting surface.
b . S h o r t D i s t a n c e M o v e m e n t . Use a forklift and
l i f t the unit at base, or carry unit to new worksite
keeping the unit vertical.
Section
III.
CONTROLS A N D
INSTRUMENTS
2-6. General
a r e listed and described in table 2-1. Figures 2-3, 2-
4 and 2-5 illustrate the controls and show their
This  section  describes,  locates,  illustrates,  and
locations.
Table  2-1  provides  the  control
furnishes the operator/crew sufficient information
nomenclature,  its  reference  designation,  a
about  the  various  controls  to  insure  proper
description of the component and a description of
operation of the air conditioner.
its function.
2-7. Controls and Instruments
T h e controls and instruments on the air conditioner
Table 2-1. Controls and Instruments
Reference
Control
Function
designator
Description
Mode Selector
S
Controls the air conditioner functions as
F o u r wafer. five position rotary
follows: COOL position: Energizes control
selector switch.
circuits for cooling and fan drive motor. De-
e n e r g i z e s heater control circuits. VEN-
T I L A T E position: Energizes fan drive
motor, de-energizes cooling and heating
circuits. OFF position: De-energizes all
operating circuits. turns the air conditioner
off. LO-HEAT position: Energizes one bank
of heaters and fan drive motor. HI-HEAT
position: Energizes primary and secondary
heaters and fan drive motor, de-energizes
cooling control circuits.
Circuit breaker reset
Knob attached to circuit reset
Pull knob out to reset circuit breaker if it
knob
mechanism.
should trip. After resetting push knob back
in. Circuit breaker should rem ain in closed
position.
High pressure cutout
Part of high pressure cutout.
Push to reset, if air conditioner should cutout
reset
due to high discharge pressure.
Low pressure cutout
Part of low pressure cutout.
Push to reset if air conditioner should cutout
reset
due to low suction pressure.
Temperature
Control
S1
Adjustable, single pole double-throw,
Provides for controlling the operation of either
Thermostat
action-thermostat with range from
the cooling circuit or heating circuit as the
+ 4 0 degrees to +90 degrees F
temperature and mode selector switch setting
with 2 degrees F differential at any
dictate.
particular setting.
S7
Fun speed switch
Single  pole  single  throw  toggle
Provides for selection of high or low speed on
switch.
the fan drive motor.
Pull chain attached to hinged door in
Fresh air damper control
Provides for controlling the amount of fresh air
the fresh air duct.
intake.

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business