TOP OF HOUSING
Avoid bodily contact with liquid refrigerant and avoid inhaling refrigerant gas. Be
especially careful that Refrigerant 12 does not come in contact with eyes. In case of
refrigerant leaks, ventilate area immediately.
4.
Discharge Refrigerant System
NOTE
In accordance with Environmental Protection Agency regulations, refrigerants cannot
be discharged into the atmosphere. A refrigerant recovery&recycling unit must be used
whenever discharging the refrigerant system.
Operation of the recovery/recycling unit must be by AUTHORIZED PERSONNEL
ONLY.
Connect and operate a recovery/recycling unit in
accordance with the manufacturer's instructions.
Refer to paragraph 5-13 and replace dehydrator.
5.
Remove valve cap from discharge and suction
Purge Refrigerant System
6.
service valves.
Using proper nitrogen regulator connect a cylinder
of dry nitrogen to suction service valve.
Attach suitable hose to discharge service valve.
Open both suction and discharge service valves.
..
Open valve on nitrogen cylinder and allow nitrogen
to flow through refrigerant system until all mois-
ture is forced out. Do not exceed 5 psig.
Close nitrogen cylinger valve.
Close suction and discharge service valves.
Remove nitrogen cylinder and discharge hose.
Using bar manifold, connect vacuum pump to cen-
ter hose. Using proper hoses, connect suction ser-
vice valve to suction pressure gage.
Turn on vacuum pump, open service valves and
hold a 29.0 inch Hg vacuum for eight (8) hours.
Close suction and discharge service valves.
Turn off vacuum pump.
Remove hoses from suction and discharge valves.
Remove vacuum pump and install valve caps.
Solder all copper-to-copper joints with silver solder
7. Soldering Procedure
type 3, 4 or 6A per specification QQ-S-561.
Solder all copper-to-brass or copper-to-steel with
type 4 or 6A per specification QQ-S-561.
Solder melting point is 1160F (625C).
Make all solder joints with an atmosphere of inert
gas to prevent internal oxidation.