TM 5-4120-356-14
LOW PRESSURE CUT-OUT RESET BUTTON
HIGH PRESSURE CUT-OUT RESET BUTTON
T h e low pressure cut-out switch
T h e high pressure cut-out switch
stops the unit if compressor suc-
s t o p s the unit if compressor diis-
t i o n pressure  f a l l s b e l o w 2 5 p s i g
c h a r g e pressure rises above 460
p s i g ( 3 2 . 3 4 3 k s / c m2 ) . T o r e s t a r t
( 1 . 7 5 8  k s / c m2 ) . To restart the
unit, wait a few minutes for the
the unit, wait a few minutes for
p r e s s u r e to increase, then push
t h e pressure to decrease, then
the low pressure cut-out reset
push the high pressure cut-out
button.
reset  button.
SIGHT GLASS
The sight glass indicates the
refrigerant moisture content.
When the indicator is green, the
refrigerant is dry (normal con-
dition). A color shading into
yellow  indicates  that  the  refrig-
e r a n t has become contaminated
with moisture. A shortage of re-
frigerant is indicated by bubbles
in the sight glass.
ELECTRICAL RECEPTACLE CONNECTOR
For connection of 208 volt, 50/60
Hz, 3-phase electrical power
source.
CIRCUIT BREAKER KNOB
The circuit breaker cuts off all
electrical power to the unit in
case of an electrical power over-
load. To reset the circuit break-
er, first pull out, then push in
the circuit breaker knob.
TS5-412035614/2-2
F i g u r e 2-2. Rear side. O p e r a t o r ' s controls and indicators