Figure 4-74. Solenoid Valves (L1 and L2)
a. Removal
(1) Discharge and purge the refrigeration system per paragraphs 4-5 and 4-6.
(2) Disconnect the two leads at the disconnect splices.
(3) Using wrench, remove the top nut that attaches the coil to the valve body.
(4) Lift the coil assembly and data plate from the body tube and plunger assembly.
4-149