ACTION
LOCATION/lTEM
REMARKS
REAR OF HOUSING
4. Rear Panel
a. Remove fourteen (14) screws securing rear panel.
b. Remove rear panel.
Test condenser coil for leaks prior to discharging refrigerant system
and removing condenser coil.
5. Refrigerant System Refer to paragraph 5-7 and discharge refrigerant system.
HOUSING INTERIOR
Loosen setscrew in hub of condenser fan and slide
6.
Condenser
Coil
a.
condenser fan towards bulkhead.
b. Remove two (2) screws securing frame to condenser shroud.
c. Remove six (6) screws securing condenser shroud to
condenser coil.
d. Slide condenser shroud back against bulkhead.
e. Unsolder and remove two (2) refrigerant lines from
condenser coil.
f. Remove four (4) screws from underside of base that
secures condenser coil to base.
g. Remove condenser coil.
5-29