Table 5-2. NORMAL   TEMPERATURE-PRESSURE   RELATIONSHIPS
Up
TM-5-4120-375-14 Air Conditioner Horizontal Compact 18 000 BTU 208 Volt 3 Phase 50/60 Hertz NSN
Next
SECTION III MAINTENANCE  PROCEDURES
TM5-4120-375-14 Table 5-1. DIRECT  SUPPORT  MAINTENANCE  TROUBLESHOOTING  (cont.) MALFUNCTION TEST OR INSPECTION CORRECTIVE  ACTION 4. COMPRESSOR RUNS BUT DOES NOT COOL. Step 1. Check sight glass for bubbles. If bubbles exist leak check system in accordance with paragraph 5-16. Replace  sight  glass  in  accordance  with paragraph 5-33. Step 2. Install gauges in accordance with paragraph 5-21. Step 3. Check Check  system  pressure  in  accordance  with Table 5-2. compressor  for  damaged  valves. Test  compressor  in  accordance  with  paragraph 5-35. 5-6