TM  5-4120-377-14 Table  4-2.  TROUBLESHOOTING MALFUNCTION TEST  OR  INSPECTION CORRECTIVE  ACTION 1. AIR CONDITIONER DOES NOT START IN ANY MODE. Step 1.  Check  to  see  if  input  power  has  been  disconnected. Connect  input  power. Step 2.  Make  sure  that  power  is  208  volt,  3  phase,  400  hertz. Connect  correct  input  power. Step 3.  Check  to  see  if  compressor  circuit  breaker  is  tripped. Slowly PULL out AND PUSH in reset knob TO RESET Circuit Breaker. TS4120-377-14/4-T42-1 Step 4. Check for loose or damaged electrical connectors or damaged wires in wiring harnesses. (See para  4-43.) Tighten  or  replace  connectors,  or  repair  damaged  wires. Step 5.  Check  fuses.  (See  para  4-52.) Replace bad fuse(s). Step 6.  Check  operation  of  the  auxiliary  switch  in  circuit  breaker  (CB1). Test  (CB1)  auxiliary  switch.  (See  para  4-51.)  Replace  circuit  breaker  if  auxiliary  switch  is defective. Step 7.  Check  operation  of  control  power  transformer  (T1). Test  transformer.  (See  para  4-50.)  Replace  transformer,  if  defective. Step 8.  Check  operation  of  RFI  Filter  (FL1)  and  d.c.  rectifier  (CR1)  assembly. Test  filter  and  rectifier.  (See  para  4-44  and  4-53.)  Replace  defective  filter  or  rectifier. Step  9.  Check  all  terminals  and  internal  wiring  within  junction  box  for  tightness  and  damage. Tighten  terminals,  or  repair  wiring  as  necessary.  (See  para  4-49.) Step 10.  Check  operation  of  mode  selector  switch  (S1). Test  switch.  (See  para  4-40.)  Replace  switch,  if  defective. Step 11.  Check  that  high  or  low  pressure  cut-out  switches  (S6  and  S7)  are  not  open. PUSH and release TO RESET. Step 12. Reset (PUSH) PRESSURE CUT-OUT switch(s) and restart unit. If  unit  does  not  start,  contact  direct  support  maintenance. 4-40

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business