NOTE
Prior to removal of old insulation, cut the new replacement material to size using the old
item as a sample.
1
Remove as much old insulation material as possible by pulling or scraping it away from the
metal surface.
WARNING
Dry Cleaning Solvent is flammable, and its vapors can be explosive. Repeated or
prolonged skin contact or inhalation of vapors can be toxic. Use a well-ventilated area,
and keep away from sparks or flame. Use goggles, gloves, and apron when appropriate.
2
Soften and remove old adhesive and gasket residue, using dry cleaning solvent and a stiff brush.
INSTALLATION
1
Cut to size.
2
Be sure that the surface to which the insulation is to be applied is clean and free of paint and old
adhesive material.
3
Coat the mating surfaces of the metal and the insulation with adhesive. Let both surfaces air dry
until the adhesive is tacky, but will not stick to the fingers.
4
Starting with an end, carefully attach the insulation to the metal. Press into firm contact all over.
5
Install all parts and covers that were removed.
6
Install air conditioner on shelter. (See WP0006.)
END OF TASK