TM 9-4120-428-14
0005 00
REFRIGERANT
SIGHT
GLASS
13. Turn the MODE SELECTOR switch to OFF. Observe that all air conditioner functions cease.
GENERAL OPERATING PROCEDURES
The Model F9000H-4SPFI air conditioner is designed for operation in a wide range of climatic conditions either continuously
or intermittently. The amount of operator attention required will vary depending on specific local conditions for each
installation. Under usual conditions, the air conditioner will be set up for the appropriate mode of operation at the beginning
of a season and will only need starting, stopping, and minor adjustments for the rest of the season. The following table
provides the recommended initial control settings to establish the desired mode of operation. Minor adjustments may be
required to obtain the desired shelter temperature and mixture of re-circulated to fresh air or the airflow patterns of
conditioned air inside the shelter.
Table 1. Initial Operator Control Settings.
MODE
MODE
CONDITIONED FABRIC
TEMPERATURE
FRESH AIR
RETURN
SELECTOR
COVER
AIR SUPPLY
SELECTOR
DAMPER
AIR
LOUVER
LOUVER
Ventilation with 100% VENT
Any Setting
Fully Closed
Fully Open
Optional
Optional
Recirculated Air
Ventilation with
VENT
Any Setting
Partially Open Partially
Optional
Rolled Up
Make-up Fresh Air
Closed
Ventilation with 100% VENT
Any Setting
Fully Open
Fully Closed
Optional
Rolled Up
Fresh Air
Heating with 100%
LOW or
Desired Temperature Fully Closed
Fully Open
Slightly Upward
Optional
Recirculated Air
HIGH HEAT
Heating with Make-up LOW or
Desired Temperature Partially or
Partially or
Slightly Upward
Rolled Up
Fresh Air
HIGH HEAT
Fully Closed
Fully Closed
Cooling with 100%
COOL
Desired Temperature Fully Closed
Fully Open
Slightly Upward
Rolled Up
Recirculated Air
Cooling with Make-up COOL
Desired Temperature Partially or
Partially or
Slightly Upward
Rolled Up
Fresh Air
Fully Closed
Fully Closed
Any Mode with Make- Desired Mode Desired Temperature Fully Open
Partially or
Optional
Rolled Up
up Air Through NBC
Fully Closed
Filters
OPERATION IN VENTILATION MODE
1. Roll up and tie the canvas cover.
2. Open evaporator discharge louvers.
3. Turn the ventilation damper actuator to open the damper door.