TM 9-4120-428-14
0005 00
Operation in Ventilation Mode - Continued
4. Partially close the evaporator intake louver blades.
5. Position the mode selector switch to VENT.
OPERATION IN HEATING MODE
1. Open the evaporator intake louver by moving the blades up or down as required.
2. Open the evaporator discharge louvers.
3. Turn the ventilation damper actuator to close the damper door.
4. Turn the temperature selector switch to the center position.
5. Position main circuit breaker to ON.
6. Position the mode selector switch to LOW HEAT.
NOTE
In LOW HEAT mode, three heaters will cycle on and off as determined by the
temperature selector switch. In HIGH HEAT mode, three heaters will be on continuously
and three will cycle on and off as determined by the temperature selector switch.
7. Operate in LOW HEAT mode until the temperature selector switch cycles the heaters off indicating that the set point
has been reached. If the temperature does not increase to the set point, position the mode selector switch to HIGH
HEAT.
8. When the temperature selector switch begins cycling the heaters, make any necessary adjustment to it until the
desired shelter temperature is maintained. Allow sufficient time for the heaters to cycle off and on between
adjustments.
NOTE
Warm air is less dense than cool air, so it has a tendency to rise. To obtain comfortable
temperatures near the floor and lower parts of the room, it is often advisable to adjust the
evaporator discharge louver blades to direct the air slightly downward.
9. Adjust the evaporator discharge louver blades to direct the airflow as desired.
OPERATION IN COOLING MODE
1. Open the evaporator intake louver by moving the blades up or down as required.
2. Open the evaporator discharge louvers.
3. Turn the ventilation damper actuator to close the damper door.
4. Turn the temperature selector switch to the center position.
5. Position main circuit breaker to ON.
6. Position the mode selector swi tch to COOL.
NOTE
The compressor operates on a 30 second time delay and will not come on with the fan
and blower motors.
The compressor will operate continuously when in the cool mode. A refrigerant bypass
circuit is activated to direct refrigerant around the evaporator coil when the temperature
selector switch cycles off.
7. Operate the air conditioner until the temperature selector switch cycles the bypass circuit indicating that the set point has
been reached.
0005 00-5