FRESH AIR DAMPER AND ACTUATOR REMOVAL, REPLACEMENT, INSTALLATION, AND ADJUSTMENT
INITIAL SETUP:
Spring Washers (2)
Tools
Push On Nut
Refrigeration Unit Service Tool Kit, WP 0000 00, Item
Equipment Condition
1
Remove Return Air Louver (WP 0021 00)
Materials/Parts
Remove Supply Air Louver (WP 0022 00)
Remove Mist Eliminator (WP 0024 00)
Self-Locking Nuts (2)
Remove Compressor (WP 0033 00)
Lock Washer
Lock Washers (3)
17
PART OF HOUSING
18
4
5
6
19
23
13
1
20
16
22
14
C
V
L
2
O
E
S
N
15
E
T
D
15
10
9
7
21
12 11
3
22
8
O
V
E
P
E
N
N
T
REMOVAL
1. Loosen machine screw (Figure 5 -1, Item1) on standoff, threaded, S (2) and disconnect the push-pull control cable
assembly (3).
2. Remove two machine screws (4), lock washers (5), and flat washers (6). Lift damper (7) from the air conditioner.
3. Remove screw (8), lock washer (9), nut (10), spacer (11), and loop clamp (12).
4. Loosen the screw (13) in the actuator plate blind nut (14) in order to free the end of the push-pull control cable (3).
0062 00-1