Table 2. Normal Operating Pressures
TEMPERATURES
PRESSURE RANGE (PSIG)
Outdoor Ambient
55 degrees F (12.8 C)
75 degrees F (24 C)
100 degrees F (38 C)
125 degrees F (51.7 C)
90 degrees F 32 C
60-70 Suction
62-72 Suction
70-80 Suction
80-95 Suction
Return Air to Unit
205-220 Discharge
225-245 Discharge
305-325 Discharge
400-425 Discharge
(Dry Bulb)
80 degrees F (27 C)
60-70 Suction
60-70 Suction
65-75 Suction
70-80 Suction
Return Air to Unit
185-205 Discharge
215-235 Discharge
290-310 Discharge
385-415 Discharge
Dry Bulb
NOTE
FOLLOW-ON MAINTENANCE:
Remove service manifold (WP 0064 00)
END OF WORK PACKAGE