TB 9-2320-279-13-1
NOTE
Push down firmly on hose connectors until a clicking sound is heard to make sure coupler is locked.
4.
Connect hose (7) to hand valve (8).
5.
Connect hose (7) and hand valve (8) to service valve (2).
6.
Connect hose (9) to hand valve (10).
7.
Connect hose (9) and hand valve (10) to service valve (4).
8.
Connect center hose (11) to recovery/recycling station (12) and receiving container (13).
9.
Open valve (14) on receiving container (13).
10. Turn knob clockwise to open hand valve (8).
11. Turn knob clockwise to open hand valve (10).
NOTE
Recovery/recycling station will also recover refrigerant oil from air conditioner system. Refrigerant oil
will be separated from refrigerant in a container on recovery/recycling station. Amount of refrigerant oil
recovered must be noted. Not all refrigerant oil will be recovered; some refrigerant oil will stay in air
conditioner system.
12. Recover all refrigerant from system to 10 to 15 in. Hg vacuum on low-side gage of recovery/recycling
station.
CAUTION
Always comply with all local regulations regarding refrigerant disposal. Failure to comply may
result in penalties for improper disposal.
Air conditioner receiver/dryer must be replaced each time air conditioning system refrigerant is
evacuated or damage to system may result.
13. Replace air conditioner receiver/dryer.
0052-49
|