|
|
TB 9-2320-364-13&P-1
7.
Connect hand valve (7) on hose (8) to service valve (2).
8.
Connect hand valve (9) on hose (10) to service valve (5).
NOTE
Perform Step (9) with engine off and low side hand valve closed.
9.
When charging from bulk container, position bulk container (11) upside down and open high side
hand valve (12).
10. Allow refrigerant to enter system until 27 oz. (765 g) has been added. Close high side hand valve (12).
11. Start engine (TM 9-2320-364-10). Position personnel cab air conditioner controls at maximum cooling
and fan speed. Refrigerant compressor must engage.
12. Shut engine OFF (TM 9-2320-364-10).
0055-58
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |