TM 10-4110-262-13&P
0002 00
EQUIPMENT DATA
Table 1. ADR-300 Technical Characteristics.
External Dimensions
Height
96 in.
244 cm
Width
88 in.
224 cm
Depth
108 in.
274 cm
Interior Dimensions
Height
81 in.
206 cm
Width
75 in.
191 cm
Depth
80 in.
203 cm
Weights
Empty
3,285 lb
1,490 kg
Maximum Gross
10,000 lb
4,536 kg
Electrical Power
208/230 VAC, 3-phase, 50-60 Hz
Refrigeration Unit
Compressor
Direct Drive, Semi-hermetic
Compressor Oil Charge
42.2 oz (1250 cc)
Compressor Oil Type
Polyol Ester
Defrost Method
Hot Gas
Defrost Timer
Initiation Interval:
Adjustable, 1 min. to 10 hr. (default 4 hr.)
Termination Interval: Temperature controlled (485.4F, 8.93 C)
Defrost Initiation Maximum Evaporator
36 F
Outlet Temperature
Refrigeration System
Refrigerant Charge and Type
4.62 lb (2.1 kg) R-404A
Inside Temperature 35 F: 9000 Btu/h
System Capacity
(External ambient temperature 110F,
Inside Temperature 0 F: 5000 Btu/h
230 VAC, 60 Hz, 3-phase power supply)
High Pressure Cutout (HPCO) Switch
Opens 450 10 psi (3120 69 kPa)
Closes 375 38 psi (2585 262 kPa)
Low Pressure Cutout (LPCO) Switch
Opens 5 11 in.Hg (-17 - -37 kPa)
Closes 4 7 psi (27.6 48.3 kPa)
Suction Pressure Regulator
65 psig
Electrical System - Fuses
Fuse 1 Evaporator Fan Motor
10 A
Fuse 2 Evaporator Fan Motor
10 A
Fuse 3 Condenser Fan Motor and
15 A
Defrost Solenoid
Fuse 4/1 Control Panel (located in
3A
control panel enclosure)
Fuse 4 Control Panel (located on PC
3A
Board in RU electrical enclosure)
Fuse 5 Transformer
4A