TM 10-4110-262-13&P
0016 00
WARNING
The RU condenser section includes moving parts that may
cause serious injury to hands or other body parts. The
unit can start at any time. Stay clear of fans when the
condenser cover is removed. Failure to comply may
result in serious injury to personnel.
6. Remove the condenser section front cover and exhaust grille and set aside. Remove the control box
cover on the electrical enclosure.
7. Inspect:
a. All refrigeration components and all refrigerant lines for evidence of leaks or damage. Copper
tubes and hoses should be free of dents and kinks. Condenser fins should be free of debris and
without damage.
WARNING
The RU electrical system includes high voltage
components that, if contacted, may cause serious injury
or death. Failure to comply may result in serious injury or
death of personnel.
NOTE
Leaks appear as a film of oil or dirt on the surface of the tube.
b. Electrical connections to ensure they are secure and free of cracks, corrosion, and moisture.
c.
Electrical enclosure
(1) Remove control box cover.
(2) Inspect electrical enclosure components for tightness of electrical connection.
(3) Note damage to components or moisture.
(4) Replace control box cover.
d. Condenser fan blade to ensure that it is undamaged and turns freely.
e. All other components to confirm they are undamaged and properly restrained.
0016 00-2
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |