Click here to make tpub.com your Home Page

Page Title: If Both Lights Don't Work
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 10-4110-262-13&P
0018 00
If Both Lights Don't Work
1. Unplug the IC power supply cable from the IC power entry connector.
2. Remove the light switch cover.
3. Remove the light switch from the box and the pull it to the extent of the wires.
4. Reconnect the power at the power entry connector.
5. Test the voltage at the black wire (35001) and the white wire (35000).
6. If line voltage is detected, go to Step 8.
7. If line voltage is not detected, isolate the fault between the power entry connector and the light switch.
8. Disconnect the RU main power supply from the ADR-300.
9. To test the light switch:
a. Disconnect the IC power supply cable from the IC power entry connector to de-energize the IC
electrical system.
b. Remove the switch cover from the light switch, remove the two screws that hold the switch in the
box, and remove the switch from the box.
c.
Test the electrical continuity between the switch terminals.
NOTE
The switch is good if there is no continuity with the switch in the OFF position and
there is continuity with the switch in the ON position.
d. If the switch is good, go to the section entitled, If the Pilot Light Works and the Interior Light Does
Not, Step 3 on the next page.
10. If the switch is not good, replace the switch (see Work Package 0022 00).
If the Interior Light Works and the Pilot Light Does Not
Replace the pilot light (see Work Package 0021 00).
0018 00-2

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business