11. Check continuity for each terminal of the connection. If any terminal does not show continuity,
replace the connector.
a. Tag wire connections to identify their correct terminals in the cannon plug.
NOTE
Two terminals are different length and diameter. Be sure to note that the
wires attach to these terminals.
b. Cut wires as close as possible to the plug terminals.
c.
Strip about in of insulation from the ends of each wire.
d. Insert the appropriate wire ends into the new odd-sized connector terminals and crimp or solder
as appropriate. Confirm that the wire-terminal joint is good.
e. Insert the remaining wire ends into the remaining terminals and crimp or solder as appropriate.
Confirm that the wire-terminal joint is good.
f.
Insert the terminals into the new connector until the terminal is seated in the connector body.
g. Assemble the connector body and housing.
h. Install the new connector in the electrical connector box.
12. If all three terminals tested in Step 11 show continuity, replace the wire from the main power
connector to the compressor motor contactor.
13. Reconnect power to the RU and check voltage at the IC power entry connector. If voltage is present,
return the ADR-300 to service.
14. Disconnect power from the RU.
15. Open the condenser section top grille.
16. Remove the transformer cover to access the transformer terminals.
17. Reconnect power to the RU.
18. Check voltage between transformer primary connections.
a. If voltage between H and H1 is NOT 110 VAC, go to Step 19.
b. If voltage between H and H2 is NOT 220 VAC, go to Step 19.
c.
Go to Step 22.
0018 00-5
|