TM 10-4110-262-13&P
0029 00
Main Power Supply
1. Check input power cable voltage.
2. Check phase-to-phase voltage for 208/230 VAC, phase-to-ground and phase-to-neutral for 120 VAC.
3. Check voltage phase-to-phase on the line side of the compressor contactor.
L1 to L2
208/230 VAC
L1 to L3
208/230 VAC
L2 to L3
208/230 VAC
L1 to ground
120 VAC
L2 to ground
120 VAC
L3 to ground
120 VAC
WARNING
Disconnect all input power. High voltage is present and
electric shock may occur. Failure to comply may result in
serious injury or death to personnel.
4. If no voltage or incorrect voltage is present at terminals L1, L2 or L3, conduct a resistance check from the plug
receptacle to t he individual terminal L1, L2, L3 and plug receptacle pins.
5. Replace defective conductor and/or receptacle if required.
Heater Circuit
1. Adjust the set point to 10 F above box temperature to initiate the heat cycle.
2. If heater rods in evaporator are not hot, check heater overload. If tripped, reset. If it trips again,
check for shorted heater or circuit.
3. If overload is not tripped, check for voltage on load side of overload.
4. If no voltage, check heater contactor control circuit.