TM 10-4130-239-14
2-7.
INITIAL ADJUSTMENTS AND DAILY CHECKS.
a .
Follow Assembly And Preparations For Use instructions before
proceding, 2-6.
b.
Inspect all covers, panels, grilles for loose mounting,
obstructions, or shipping damage.
Report any deficiencies to unit
maintenance.
c.
Perform the preventive maintenance checks and services listed
in table 2-1.
2-8.
OPERATING PROCEDURE.
WARNING
Calcium hypochlorite can cause serious injury
if not handled properly.
Heed all safety
measures below.
If calcium hypochlorite comes
into contact with skin or eyes, flush right
away with water.
Get medical help.
Mix only in accordance with directions for
use.
DO NOT allow calcium hypochlorite to mix
with any other materials, such as fuels, oils,
paint products, or ammonia.
This may cause
fire or hazardous gases.
CAUTION
Store calcium hypochlorite in cool, dry place.
Keep container closed.
NOTE
Before using the water chiller after shipment or
repairs, the system must be purged with
disinfectant.
a.
Purginq the Water System.
1 Fill two 5-gallon (19-liter) pails with water.
Add 0.1 ounce
(2.8 grams) of calcium hypochlorite powder (item 8, appendix
E) to each.
Stir each pail with a wooden paddle until powder
is dissolved.
2-19
|