TM 5-4110-217-14
CHAPTER 3
OPERATOR AND ORGANIZATIONAL MAINTENANCE
INSTRUCTIONS
Section I. REPAIR PARTS, SPECIAL TOOLS AND EQUIPMENT
3-1. Special Tools and Equipment.
3-3. Organizational Maintenance Repair Parts.
Organizational maintenance repair parts are listed
No special tools or equipment are required by the
and illustrated in TM 5-4110-217-24P.
operator or organizational maintenance personnel for the
refrigeration unit.
3-2. Basic Issue Tools and Equipment.
Not applicable.
Section II. LUBRICATION INSTRUCTIONS
d. Precautions. Before lubricating the equipment,
3-4. General Lubrication Information.
be sure that the starter switch is OFF. Otherwise,
automatic controls may start operation of the equipment
a. This section contains the lubrication chart and
and cause injury to personnel.
lubrication instructions which are supplement to, and not
e. Engine Oil. (Model RMP-J/1-1OG)
specifically covered in the lubrication chart.
(1) The crankcase oil level must be checked
b. The lubrication chart, figure 3-1, is the
frequently, as oil consumption may increase.
approved lubrication chart for the gasoline engine driven
(2) The oil may require changing more
unit model RMP-J/1-1OG. Other than the power source,
frequently than usual, because contamination by dilution
the electric motor driven model RMP-J/11-1OE has the
and sludge formation will increase under cold weather
same lubrication. No lubrication is required for the
operation conditions.
electric motor.
f. Air Cleaner Service. (Model RMP-J/1-1OG)
(1) Remove wing nut and lift off cover and
filter element as indicated in figure 3-2.
3-5. Detailed Lubrication Information.
(2) Clean bowl, cover and filter element with
a. General.
Keep all lubricants in closed
an approved cleaning agent.
containers and store In a clean, dry place away from
(3) Fill bowl to oil level with same grade of oil
external heat. Allow no dust, dirt, or other foreign
used in engine crankcase.
material to mix with the lubricants. Keep all lubrication
(4) Replace filter element every 200 hours of
equipment clean and ready for use.
operation.
b. Cleaning. Keep all external parts not requiring
(5) Assemble air cleaner as shown in figure 3-
lubrication, clean of lubricants. Before lubricating the
2.
equipment, wipe all lubrication points free of dirt and
NOTE
grease. Clean all lubrication points after lubricating to
This service will vary from several
prevent accumulation of foreign matter.
days
during
operation
in
c. Points of Lubrication. Service the lubrication
comparatively clean conditions, to
points at proper intervals as illustrated in figure 3-1.
twice a day in dusty conditions.
g. Every 1000 operating hours, lubricate fan
shaft and pulley bearings with BR.
h. Check the compressor oil level, paragraph
Change 3 3-1
|