(3) Suction tubing remains abnormally warm.
6-8. Removing Moisture.
b.  Valve Frozen Open. If the expansion valve is
frozen open.
the following characteristics may be
The following means may be used to remove
observed.
moisture from the refrigeration system It will be
(1) Suction pressure remains abnormally high.
necessary to artificially warm the expansion valve or shut
(2) Compressor pounds.
off and warm the entire unit for a long enough period of
c.  Liquid Moisture Indicator If color indicator is
time to thaw the frozen water in the system, enabling It to
pink, moisture is present in system.
be recirculated with the refrigerant
6-2.1/(6-2.2 blank)