TM5-4110-234-14
TO 40R7-5-7-1
(3)
Tag and remove the wires.
(4)
Remove the nuts, lock washers, and clamp that secure the gage to the control panel.
(5)
Pull the gage from the front of the control panel.
b.
Installation.
(1)
Install the gage through the panel and clamp in place using the clamp, nuts and lock washers supplied
with the gage.
(2)
Connect the wire leads. See tags and wiring diagram figure 4-6.
(3)
Close the hinged control panel and secure with two screws and lock washers.
(4)
Connect power.
4-25.
CIRCUIT BREAKERS I See figure 4-14.
a. Removal.
(1)
Disconnect power.
(2)
Remove the two screws and lock washers and open the hinged control panel.
(3)
Tag and remove the wires.
(4)
For testing of installed part see step b.
(5)Detach retaining clip and remove circuit breaker.
b. Testing. With leads disconnected check resistance of circuit breaker. For Model F10000R-6 the resistance
should be 0.09 ohms. For Model F10000RG-2 the resistance should be 12.0 ohms.
c. Installation.
(1)
Insert circuit breaker into panel and secure it in place with press-on retaining clip.
(2)
Connect the wire leads. See tags and wiring diagram figures 4-5 or 4-6.
(3)
Close the hinged control panel and secure with two screws and lock washers.
(4)
Connect power.
4-26.
DEFROST IN PROGRESS LIGHT See figures 4-14 and 4-16.
a. Bulb removal.
(1)
Unscrew the lens and lens holder.
(2)
Push in and turn bulb counterclockwise.
(3)
Check bulb for loose or broken filaments.
b.
Bulb replacement.
(1)
Insert bulb, push and turn clockwise.
(2)
Screw lens and lens holder in place finger tight.
4-38
|