TM5-4110-234-14
TO 40R7-5-7-1
a.
Removal.
(1)
Disconnect power.
(2)
See figure 4-12 and remove the evaporator air housing and screen.
(3)
Remove two screws and lock washers and open the control panel door.
(4)
Remove the tube clamps and carefully cut the plastic tie wraps that hold the capillary line in place.
(5) Carefully thread the capillary line and bulb through the heat shield wall. Take care not to damage the
other capillary lines.
(6)
Remove the two screws and lock washers and remove the defrost timer.
(7)
Tag and disconnect the wires.
b.
Inspection.
(1)
Inspect for physical damage.
(2) Inspect for signs of overheating.
c.
Testing. Perform continuity checks with ohmmeter as follows:
(1)
There should be continuity between terminals 1 and 3.
(2)
There should be continuity between terminals 3 and 4.
d.
Installation.
(1)
Thread the capillary down through the grommeted hole in the bottom of the control box.
(2)
See wiring diagram figure 4-5 and connect wire leads.
(3)
Secure the defrost timer with two screws and lock washers.
(4)
Thread the capillary through the heat shield wall.
(5) Clamp the capillary end to the evaporator coil header as shown on figure 4-19. At least 6 inches
(15.2cm) of the capillary end must make contact with the header.
(6) Reclamp the capillary line in its original clamps. Install new plastic tie wraps or use electricians tape to
secure the capillary lines together.
(7)
Check to see that grommets are in place at heat shield wall.
(8)
(9)
Close the control panel and secure with two screws and lock washers.
(10) Close access doors and connect power.
4-32.
DEFROST TIMER (MODEL F10000RG-2) I See figure4-3.
a. Removal.
(1) Disconnect power.
4-44
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |