Order this information in Print

Order this information on CD-ROM

Download in PDF Format

     

Click here to make tpub.com your Home Page

Page Title: CHAPTER 2 OPERATING INSTRUCTIONS
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books
   

 

CHAPTER   2 OPERATING    INSTRUCTIONS Section   1.   SERVICE   UPON   RECEIPT   OF   EQUIPMENT 2-1.   Inspecting   and   Servicing   Equipment a.  Inspection.   Inspect  entire  air  conditioner  for signs of damage, missing or loose hardware and any defects   that   may    have  been  incurred  during shipment.  Make  a  thorough  check  to  see  that  all wiring,  lines,  and  tubing  are  secure;    and  pay particular   attention   to   the   evaporator   and   con- denser  coils  and  main  power  receptacle  connector. Be sure that all visible wiring and insulation is not frayed   or   broken.    Check   the   evaporator   and condenser  fan  motors  for  free  rotation.  Report  all dam age and defects to organizational maintenance. b.  Servicing.   Perform   the   daily   preventive checks and services listed in table 3-1. Be sure all hardware  is  securely  in  place. 2-2.  Installation   or   Setting   up   Instructions a.  General.  Both  the  evaporator  and  condenser are  fitted  for  mounting  to  a  vertical  wall  or  on  a base.  A  layout  of  the  holes  required  to  mount  the units  on  a  vertical  wall  by  means  of  the  side brackets is given in figure 1-7. The layout for holes necessary for base mounting is given in figure 1-6. Care and judgement should be exercised in locating the  units.  The  prime  consideration  for  the  con- denser is that there should be free access for outside air to and from the condenser coil. Keeping in mind that   intake   air   is   through   the   expanded   metal screen  in  front  of  the  condenser  section  and  that discharge  is  outward  through  the  condenser  coil, locate  the  unit  so  that  there  is  a  minimum  of  14 inches of free space in front of the unit. If possible, do not place the unit so that prevailing winds blow toward  face  of  the  coil,  and  do  not  locate  where intake air is likely to be laden with dust, dirt, soot, smoke  or  other  debris.  The  evaporator  section  is similarly designed for base mounting or side-angle mounting  to  a  vertical  wall.  Location  of  this  unit should be determined mainly by the internal layout of   the   enclosure   to   be   conditioned.   As   far   as possible, locate the unit so that the conditioned air discharges toward the area most critically in need of cooling.   (The   direction   of   discharge   can   be   con- trolled  to  some  extent  by  adjustment  of  discharge air  louvers.  Installation  should  provide  for  easy access  to  the  front  of  the  unit  in  order  that  filters may   be   changed   and   that   controls   may   be manipulated.  Fresh  air  intake  is  through  the  back of the unit, which will necessitate a hole cut into the enclosure’s wall. Some compromise may have to be made  once  the  locations  for  each  unit  have  been selected, since these relative locations are restricted by  the  length  of  the  connecting  refrigerant  hosing and  electrical  cabling.  The  location  of  each  unit must provide for an adequate flow of air to and from the  unit.  Before  mounting  either  one  of  the  units, check to see that the hoses will reach between the units. b.   Connections. (1) Connect both ends of the larger refrigerant line  to  the  fittings  marked  “S”  on  each  of  the  two section. Use two wrenches, one to hold the fitting on the unit stationary, the other to tighten the coupling to  approximately  35  ft.  lbs.  of  torque. Caution:   Do  not  allow  the  fitting  on  the unit  to  turn.  Avoid  kinking  or  twisting  the  hose. (2) Connect the smaller refrigerant hose to the fittings   marked   “D”. (3)  Open  the  receiver  valve.  This  valve  is located  in  the  condensing  section  immediately behind  the  air  intake  grille.  (fig.  1-5).  Remove  the valve stem cap to expose the stem. Turn this stem counterclockwise as far as it will go and replace and tighten  cap.  A  slight  hissing  sound  may  be  heard during  this  process  as  the  refrigerant  is  released from  the  tank  into  the  system. (4)  Connect  the  electrical  cable  between  the receptacles marked  “L”  with  the  female  end  of  the cable going to the evaporator section. Since a time delay is not used, thereceptacle on each condensing unit  must  be  shorted  out  with  the  plug,  which  is chained  to  the  receptacle. (5)  Connect  the  power  supply  (4-wire  cable). One  end  of  this  cable  contains  a  female  connector which  is  to  be  attached  to  the  receptacle  marked “P” on the condenser section. The other end of the cable is to be connected to the power supply. (a) Set  switch  #  3  to  “VENT”  position  and switch  #  2  to  “ON”. (b)  Turn  on  power. (c)  Observe   rotation   of   evaporator   fan motor, (this should be the only fan operating at this setting). Rotation should be counterclockwise when looking  down  into  the  evaporator  section.  Double check by noting that air is being discharged out of the four discharge air grille louvers, just above the 2-1

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business