Capacity . . . . . . 9,000 BTU/HR
military model number, federal stock number,
S t o c k Number . . . . . FSN 4120-831-8238
aerial number, specification number, part number,
Manufacturer . . . . . . . Harvey W. Hottel, Inc.
contract number, date, weight and capacity.
(2) C o m p r e s s o r i d e n t i f i c a t i o n p l a t e . L o c a t e d
(2) E v a p o r a t o r a n d c o n d e n s e r f a n m o t o r .
on the front of compressor housing. Specifies
Manufacturer . . . . . . . . Welco Industries
compressor model number, part number, serial
Part Number . . . . . . . . . . . . . 4715-18
Hp (Horsepower) . . . . . . . . . . .86/.10
number, refrigerant, oil type and capacity,
Type . . . . . . . . . . . . . . . . . . . . Double extended shaft
manufacturer and complete electrical data.
Volts . . . . . . . . . . . . . . . . . . 115
(3) F a n m o t o r i d e n t i f i c a t i o n . L o c a t e d o n t o p
Amp (amperes) . . . . . . . . . . 8.0/1.40
o f the fan motor. Specifies motor horsepower, serial
Frequency . . . . . . . . . . . . . . . .60 Hertz
num her, rpm ( r e v o l u t i o n s p e r m i n u t e ) , a n d
Phase . . . . . . . . . . . . . . . . . . . .1
e l e c t r i c a l characteristics.
RPM . . . . . . . . . . . . . . . .3450/1750
Duty . . . . . . . . . . . . . . . . . . . . . Continuous
(4) Control panel legend plate. L o c a t e d o n
Drive . . . . . . . . . . . . . . . . . . . Direct
the front of the unit control panel. Indicates unit
t e r m p e r a t u r e setting for cooling or heating purposes,
(3) P e r f o r m a n c e D a t a .
mode selector switch and fan speed switch.
Cooling Capacity . . . . . . . . . .9,000 BTU/HR nominal
(5) W i r i n g d i a g r a m p l a t e . L o c a t e d o n i n s i d e
9,500 BTU/HR actual at
1 2 0 F DB, Air to Con-
of front access panel, illustrates complete unit
d e n s e r , 90 F DB, 75 F
wiring.
WB, return air to unit.
(6) R e f r i g e r a n t 2 2 p l a t e . L o c a t e d o n t h e r e a r
Capacity
6,000
BTU/HR
(hi-beat
and
panel in upper left area. It states that the unit is
h i - s p e e d positions) 3,000
charged with 3.31 pounds of refrigerant 22.
BTU/HR (lo-heat and hi-
speed positions)
(7) Color indicating plate. Located on the
rear panel immediately above the liquid line sight
(4) D i m e n s i o n s a n d w e i g h t .
glass. It has three color bands: green, chartreuse,
Length . . . . . . . . . . . . . . . . . 17 in.
a n d yellow which are used in conjunction with the
Width . . . . . . . . . . . . . . . . . . . 17 in.
l i q u i d sight line glass to indicate moisture condition
Height . . . . . . . . . . . . . . . . . .32 1/8 in.
Weight . . . . . . . . . . . . . . . . . 170 lbs.
of the refrigerant.
(8) High and low pressure cutout control reset
(5) E v a p o r a t o r a n d c o n d e n s e r f a n s .
plate. Located on rear panel at the high and low
Manufacturer . . . . . . . Harvey W. Hottel, Inc.
pressure cutout control reset buttons with
Type
.
.
.
.
.
.
Condenser-propeller,
nomenclature: " P U S H T O R E S E T " .
Evaporator-centrifugal
(9) Indicating arrow plate, L o c a t e d o n t h e
Number per unit . . . . . . . .1 each
Rotation (facing condenser
rear panel just above the condenser fan guard; the
air discharge grille) . . Clockwise
a r r o w indicates direction of condenser fan rotation.
(10) C o m p r e s s o r circuit breaker reset
(6) C o m p r e s s o r r e l a y .
plate. Located on the lower right side of the air
Manufacturer . . . . . . . . . . . . Cutler-Hammer
conditioner. It states: " C I R C U I T B R E A K E R
Part Number . . . . . . . . . . . . .MS24192-D1
AMP. . . . . . . . . . . . . . . . . . . . .25
RESET".
Type . . . . . . . . . . . . . . . . . . . . Three pole, single throw
(11) Refrigerant piping plate. Located on
norm ally open
outside of front access panel.
Coil voltage . . . . . . . . . . . . ..28 VDC
(12) Service gage plates, Located beside the
(7) Temperature
control
thermostat.
access cover on the rear panel. They state:
Manufacturer
Penn
Controls
"SUCTION
SERVICE
VALVE"
and
A19AGF-10
Part Number . . . . . . . . .
"DISCHARGE SERVICE VALVE",
Action . . . . . . . . . . . . . . . . . . . Single pole, double throw
(13) C o m p r e s s o r circuit breaker reset
Range . . . . . . . . . . . ..+40 F to 90F
p l a t e . Located on the back of the unit on the CBR
Differential . . . . . . . . . . . . . . 2 F
duct cover. It states: " P U L L A N D P U S H T O
Electrical rating . . . . . . . 5.8 Amps at 120 VAC
RESET CIRCUIT BREAKER".
(8) Mode selector switch.
(14) Damper operation plate. Located on
Manufacturer
Cutler-Hammer
return air grille on front of air conditioner. It
Type . . . . . . . . . . . . . . . . . . Rotary (Manual)
states: "FRESH AIR DAMPER CHAIN PULL
Part Number . . . . . . . . . . . . . 8912K216
TO CLOSE".
Number of positions . . . . . . 5 (hi-heat, lo-heat. off, ven-
b. Tabulated Data.
tilate, cool)
Electrical rating . . . . . . . . 15 amp. 250 VAC
(1) A i r c o n d i t i o n e r i d e n t i f i c a t i o n p l a t e .
Air conditioner . . . . . Vertical. compact, Harvey W.
(9) F a n s p e e d s w i t c h .
Hottel Model CV-9-5/6-15,
Type . . . . . . . . . . . . . . . . . . .. Single pole
Specification
MIL-A-
Part Number . . . . . . . . . MS24523-22
32513A(ME), Class 1, 115
Position . . . . . . . . . . . UP-Hi speed, DOWN-lo speed
Volts A.C., 60 Hertz, 1
Electrical rating . . . . . . . . . . 15 Amps at 28 VDC
phase.
1-5
|