Table 3-2. Organizational Troubleshooting (continued)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
AIR CONDITIONER NOISY DURING OPERATION (continued)
Step 2.
Loose component
Tighten component.
3.
INSUFFICIENT COOLING
Step 1.
Thermostat improperly set.
Set thermostat for cooler operation. (Refer to figure 2-1.)
Step 2.
Refrigerant low or contaminated.
Check sight glass. If refrigerant appears yellow rather than green, or if bubbles
appear in the refrigerant, report the condition to Direct Support Maintenance.
4.
NO COOL AIR DISCHARGE
Step 1.
Selector switch in wrong position.
Set selector switch for cooling. (Refer to figure 2-1.)
Step 2.
Thermostat improperly set.
Set thermostat for desired temperature. (Refer to figure 2-1)
Step 3.
Air filter is dirty or clogged.
Remove and clean air filter. (Refer to paragraph 3-9h.)
Step 4.
High pressure cut-out switch tripped.
Reset high pressure cut-out switch. (Refer to figure 2-2.)
Step 5.
Low pressure cut-out switch tripped.
Reset low pressure cut-out switch. (Refer to figure 2-2.)
5.
EXCESSIVE COOLING
Step 1.
Thermostat set for too cool operation.
3-6
|