TM 5-4120-341-13
Remove twelve (12) screws
Air Filter
1
securing air filter cover to
bottom of air conditioner.
Remove air filter cover and
gasket.
Slide air filter down and out
of air conditioner.
Dry cleaning solvent, P-D-680 or P-S-661, used to clean parts is potentially
dangerous to personnel and property. Avoid repeated and prolonged skin
contact. Do not use near open flame or excessive heat. Flash point of solvent
is 100 F (38 C).
Clean air filter with P-D-680 or
P-S-661 dry cleaning solvent or
warm soapy water and dry with low-
pressure compressed air.
Inspect air filter for damaged
or clogged condition. Replace
air filter if damage is indicated.
Inspect two (2) rubber pads on bottom
of air filter for damage. Replace
pads if damage is indicated. Secure
pads with adhesive per specification
MMM-A-121.
Dip or spray air filter with filter-
kote or oil per specification MlL-L-2104
Grade 20, 30 or better. Drain off
excessive oil before installation.
Slide air filter up into air
conditioner.
InstalI gasket and air filter cover
and secure with twelve (12) screws
NOTE
For the following PMCS items, the air
conditioner must be removed.
4-9
|