TM 5-4120-341-13
REMARKS
LOCATION/lTEM
ACTION
INSPECTION AND SERVICE
Inspect gasket for damage or deterioration.
2. Air Filter Cover Gasket
Replace gasket with rubbber per specification
ASTM D2000,2BG505F17L14.
WARNING
Dry cleaning solvent P-D-680 or P-S-661, used to clean parts is potentially
dangerous to personnel and property. Avoidatad and prolongesd skin skin
contact. Do not use near open flame or excessiva eat Flash point of solvent
is 100 F (38).
WARNING
Do not use compressed air for cleanin purposes except where reduced to
less than 30 psi and than only with efective chip uamlina and personal
-
protective
equipment
a.
3. Air Filter
Clean air with P-D-680 or P-S-661 dry
cleaning solvent or warm soapy water.
b.
Dry air filter with low pressure compressed
air.
c.
Inspect air filter for damaged or clogged
condition.
d.
Replace air filter if damage is indicated.
e.
Inspect two (2) rubber pads on bottom of air
filter for damaged condition.
f
Replace pads with a 2-inch long piece
accordance
rubber
D2000-2BG505F17L14.
Secure with adhesive per specification
9.
Dip or spray-air filter with filterkote or oil per
h.
specification MIL-L-2104 Grade 20, 30 or
i.
Drain off excess oil before installation.
BOTTOM OF HOUSING
a.
Slide air filter up into air conditioner.
4. Air Filter
b.
Install gasket and air filter cover.
Secure air filter cover with twelve (12) screws.
c.
4-33
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |