TM 5-4120-341-13
REMARKS
LOCATION/lTEM
ACTION
TOP OF HOUSING
3. Start Relay
Slip two
(2) tywraps from around start relay.
Remove
protective cover.
a.
c.
Tag and
disconnect electrical leads from start
relay.
d.
Remove
one (1) screw and self-locking nut
securing
Remove
electrical lead and start relay.
e.
4. Start Relay
a.
Tag and disconnect electrical leads from start
b.
Using an
ohmmeter, measure continuity
across start relay terminals.
c.
Replace start relay if there is NO continuity.