TM 5-4120-352-14
OPERATOR'S MAINTENANCE OF AIR CONDITIONER
Section IV.
3 - 1 0 . Liquid Sight Indicator.
3-7.
General.
Wipe refrigerant liquid sight indicator glass with
This section contains maintenance procedures
a soft clean cloth. Set controls at cool-cooler and
for the operator of the air conditioner.
operate unit for 15 minutes before observation. Yel-
low appearance indicates moisture in system and
3-8.
Screen.
bubbles or milky flow indicates low refrigerant
Remove any obstructions. Brush off loose dirt
charge. Report presence of these conditions to direct
and wipe clean.
support maintenance.
Drains.
3-9.
Clean out drain openings and remove any
obstructions.
3-3
|