opening is coved by an access cover during normal
e. Condenser Louver Control Adjustment. To
operation. A canvas cover, mounted on the rear cov-
adjust the louver control with refrigerant in the
er, is used to cover the condenser and fresh air open-
system, proceed as follows:
ings when the air conditioner is not in use.
(1) Turn off air conditioner and wait four
b. Removal.
hours or until air conditioner is uniformly at ambi-
(1) To remove front cover, remove eight
ent temperature.
screws (fig. 4-5) and remove front cover.
(2) Loosen mechanical post screw (fig. 4-4).
(2) To remove access cover (fig. 4-5), remove
Close condenser louvers, pull wire tight and tighten
four screws and remove cover.
mechanical post screw. Louvers must be tightly
(3) To remove rear cover (fig. 4-5), remove
closed when air conditioner is off.
three screws and lockwashers and remove con-
denser cover. Remove seven screws and rear cover.
4-21.
H o u s i n g Covers.
(4) The front and rear covers must be removed
a. General. The top of the housing is enclosed
before removing the center cover (fig. 4-5). Remove
by front, center and rear covers. The rear cover has
six screws. Remove two screws securing thermo-
an access opening over the charging valves. This
static switch bracket to cover.