|
|
TM 5-4120-352-14
CHAPTER
6
REPAIR INSTRUCTIONS
Section I.
REFRIGERATION SYSTEM
tally automatic and also may occur at extreme con-
6-1.
General
ditions in an attempt to maintain the suction pres-
The refrigerant system illustrated by the refrig-
sures (even during the cooling mode) at a condition
erant flow diagram (fig. 5-1), is a mechanical, vapor
above 55 psig (380 kPa) and the suction tem-
cycle type circuit consisting of the evaporator, ther-
peratures (measured at the quench bulb well) below
mal expansion valve, motor-compressor, condenser,
75F (24C). The condenser louvers are operated by
and the necessary valves and cutout devices for au-
a refrigerant powered piston located in high pres-
tomatic control during operation. The thermal ex-
sure part of the system. This piston should be fully
pansion valve releases high-pressure liquid refrig-
extended (louvers open 80F (27C) (approx.) at 250
erant into the evaporator at reduced pressure. The
psig (1140 kPa) head pressure and fully closed at
liquid refrigerant begins to vaporize by absorbing
165 psig (1140) kPa). Failure to perform this func-
heat from the air passing over the external surface
tion could result in icing of the evaporator coil and/
of the evaporator coil. The heated vapor is sucked
or cutout on the low pressure cutout.
out of the evaporator section by the motor-com-
pressor and forced into the condenser section under
6-2.
Pressure Testing the Refrig-
high pressure where it is cooled and condensed back
erant System
into a liquid. The heat released during condensation
is carried off by the condensing air stream. The liq-
a. General. A pressure test will indicate
uid refrigerant flows from the condenser to a re-
whether the air conditioner is operating at normal
ceiver, to a subcooler, and then to the thermal ex-
or at abnormal pressures. When the air conditioner
pansion valve. If the temperature control switch
is not operating at normal pressures the cause
(evaporator return air thermostat) becomes satis-
should be ascertained and corrected. Refer to table
fied, or the evaporator return air temperature is
5-1 for troubleshooting chart.
lower than the control switch set point, the re-
b. System Pressure Test. Remove caps from
frigerant system will switch to a by-pass condition.
high and low pressure service valves (fig. 5-7), con-
The temperature control switch will activate the
nect suction and discharge pressure gages to their
normally-open liquid bypass solenoid valve, closing
respective service valves. Compare the gage reading
the valve, and therefore shutting off the evaporator
with the normal range of system pressure shown in
section of the unit. The motor-compressor will con-
tinue to pump as usual and the suction pressure will
begin to drop. When it reaches approximately 65
6-3.
S e r v i c i n g Refrigerant System
psig (450 kPa), the pressure regulating valve will
a. General. When the air conditioner must un-
start to open in an effort to maintain the suction
dergo maintenance that requires opening the sys-
pressure above 55 psig (380 kPa) (approximately).
tem, the system must be discharged prior to mainte-
As the suction temperature increases, due to the
nance, then purged, a new dehydrator installed, and
pressure regulating valve opening, the quench ex-
the system charged after maintenance. Basic pro-
pansion valve will start to meter liquid refrigerant
cedures involved in servicing the refrigerant sys-
into the suction line in an effort to maintain the
tem are as follows:
suction temperature below 75F (24C) (approx.), or
b. Discharging and Purging System. Refer to
30F (-1C) super-heat (approx.). This action (the
pressure regulator and quench valve actions) is to-
ing the refrigerant system.
6-1
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |