TM 5-4120-356-14
T a b l e 3-2. Organizational Troubleshooting (continued)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
AIR CONDITIONER NOISY DURING OPERATION (continued)
Step 2.
Loose component.
Tighten
component.
INSUFFICIENT COOLING
3.
Thermostat improperly set.
S t e p 1.
Set thermostat for cooler operation. (See figure 2-1.)
Refrigerant low or contaminated.
Step 2.
Check sight glass. I f r e f r i g e r a n t a p p e a r s y e l l o w r a t h e r
than green, or if bubbles appear in the refrigerant, re-
port the condition to Direct Support Maintenance.
4. NO COOL AIR DISCHARGE
Selector switch set in wrong position.
S t e p 1.
Set selector switch for cooling. (See figure 2-1.)
Thermostat improperly set.
S t e p 2.
Set thermostat for desired temperature. (See figure 2-1.)
Air filter is dirty or clogged.
Step 3.
Remove and clean air filter. (Refer to paragraph 3-9l)
Step 4.
High pressure cut-out switch tripped.
Reset high pressure cut-out switch. (See figure 2-2.)
Step 5.
Low pressure cut-out switch tripped.
Reset l o w p r e s s u r e c u t - o u t s w i t c h . ( S e e f i g u r e 2 - 2 . )
5. EXCESSIVE COOLING
Thermostat set for too cool operation.
Step 1.
Reset t h e r m o s t a t f o r t e m p e r a t u r e d e s i r e d . ( S e e f i g u r e 2 - 2 . )