4120-01-069-1321)">

 

Click here to make tpub.com your Home Page

Page Title: DIFFERENCES BETWEEN MODELS
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 5-4120-359-14
(1) DELETED
(2) FRESH AIR DUCT - Provides filtered outside air for ventilation. May be mounted on opposite side by
exchanging it with FRESH AIR COVER, item 3.
(3) FRESH AIR COVER - Seals alternate FRESH AIR DUCT opening closed. See item 2 above.
(4) FRESH AIR FILTER - Filters the fresh (outside make up) air.
(5) POWER CONNECTOR (J1) - Connection point for input 208 volt, 3 phase, 400 Hz power cable.
(6) REMOTE CONTROL CONNECTOR (J7) - Connection point for remote control cable.
(7) TEMPERATURE CONTROL (A1-R1) - Allows adjustment and control the temperature when operating in the
cool or heat modes.
(8) RUN INDICATOR LIGHT (XDS1) - Lights when the unit is operating. Also lights when pressed in (for test
purposes) power is connected.
(9) MODE SELECTOR SWITCH (S1) - Allows operator to select COOL, OFF, LOW HEAT or HIGH HEAT
operating mode.
(10) TIME TOTALIZING (HOUR) METER (M1) - Indicates operating time (elapsed) in a modes.
(11) SIGHT GLASS - Allows visual inspection and indicates the condition of the liquid refrigerant when the unit is
operating in the COOL mode.
(12) LOW SIDE SERVICE VALVE - Provides a connection point for maintenance, testing, and service.
Unauthorized personnel should not tamper with this valve.
(13) HIGH SIDE SERVICE VALVE - Provides a connection point for maintenance, testing, and service.
Unauthorized personnel should not tamper with this valve.
(14) HIGH PRESSURE CUTOUT (SWITCH) RESET (4) - Permits manual closing (reset) of switch following
system shutdown due to excessive refrigerant system pressure.
1-9. DIFFERENCES BETWEEN MODELS
(1) Throughout this manual the following model numbers are assigned these codes:
Code:
Model Number
DHF
F18H4-2 (Keco)
EKP
MSP16-4-08 (Airtacs)
FGG
FAC-MH-18S (Ferange)
(2) The condenser sections are wired differently. Sheet 3 of figure 4-3 shows wiring for the DHF version. Models
EKP and FGG have the following differences:
a. Jumper added between K1-11 and TB3-5.
b. Wire from J13-L is connected to terminal K1-12 instead of K1-X1.
c.  TB4-12 connections are made to TB4-10.
(3) There are no differences between Model EKP and FGG.
1-4 Change 6

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business