TM 5-4120-359-14
Table 4-1. TROUBLESHOOTING (cont.)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
(4) Change damaged parts.
(5) Apply power.
Step 4.
Check condenser section.
(a) Remove Power.
(b) Remove top cover, condenser.
(c) Examine all parts and attaching hardware.
(d) Check blower impeller for interference or being out of round.
(e) Are parts firmly attached? Does impeller spin freely without wobble?
(f) Check compressor mounting.
(1) Tighten loose screws.
(2) Install missing screws, clamps, and brackets.
(3) Adjust position of impeller until it spins freely.
(4) Change damaged parts.
(5) Apply power.
4-14
|