4-57. HARNESSES AND LEADS, CONDENSER ASSEMBLY
Preliminary Procedures:
1. Remove air conditioner from shelter. (See paragraph 3-6.)
2. Remove (evaporator) access cover. (See paragraph 3-14.)
3. Remove top condenser cover. (See paragraph 3-25.)
4. Remove right end condenser cover. (See paragraph 3-26.)
5. Remove left end condenser cover. (See paragraph 3-27.)
a. Removal
(1) To remove P9A wiring harness:
Disconnect P9A connector plug at evaporator or access box.
Using screwdriver and wrench, remove screw, nut, and clamp. (Also holds P2 harness.)
Tag and remove leads to terminal board TB4 and ground E3.
(2) To remove P2 wiring harness:
Disconnect P2 connector plug at evaporator access box.
Using screwdriver and wrench, remove screw, nut, and clamp. (Also holds P9A harness.)
Tag and remove leads to terminal board TB4 and ground E3.