TM 5-4120-359-14
d. Installation- Model DHF
(1) Place actuator bracket in unit and aline holes.
(2) Using screwdriver, secure bracket to housing with three screws.
(3) Slip push-pull control cables through the two end holes.
(4) Using wrench, secure the two push-pull control cables with nuts.
(5) Insert control wires into push-pull controls.
(6) Position cylinder and insert mounting studs through bracket.
(7) Using wrench, secure cylinder to bracket with two lock nuts.
(8) Using screwdriver and wrench, secure the two push-pull control wire ends to the actuator rod with two screws
and lock nuts.
(9) See paragraph 4-60.d for outlet vane adjustment.
e. Installation - Models EKP and FGG
(1) Place actuator bracket in unit and aline holes.
(2) Using screwdriver, secure bracket to housing with two screws.
(3) Slip push-pull control cables through the two end holes.
(4) Using wrench, secure the two push-pull control cables with nuts.
(5) Insert control wires into push-pull controls.
(6) Position cylinder and insert mounting studs through bracket.
(7) Using wrench and screwdriver, secure cylinder to bracket with two lock nuts and screw.
(8) Using screwdriver and wrench, secure the two push-pull control wire ends to the actuator rod with two screws
and lock nuts.
(9) See paragraph 4-60.d for outlet vane adjustment.
Follow-on Procedures: 1. Install the top condenser cover. (See paragraph 3-25.)
2. Install right end condenser cover. (See paragraph 3-26.)
3. Install air conditioner on shelter. (See paragraph 3-6.)
4. Connect power.
4-160 Change 5
|