4120-01-069-1321)">

 

Click here to make tpub.com your Home Page

Page Title: Figure 4-98. Time Delay Relay (K6)
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 5-4120-359-14
Figure 4-98. Time Delay Relay (K6)
(7) Turn mode selector switch to COOL and temperature control to maximum COOLER.
(8) Multimeter should show 25 to 31 Vdc for 15 to 60 seconds and then zero Vdc across terminals 1 and 2.
(9) Turn mode selector switch to OFF.
(10) Disconnect power.
b. Inspect
(1) Check for loose terminal connections. Repair or replace all loose connections.
(2) Check for cracks, evidence of overheating, and other visible damage. Replace if damaged.
4-197

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business