TM 5-4120-364-13
(2) Cleaning. C l e a n all parts with a damp cloth and dry thoroughly.
(3)
Inspection.
( a ) I n s p e c t c o v e r s and panels for dents or other damage.
(b) Inspect fasteners and receptacles for security of attachment.
( c ) I n s p e c t g a s k e t s for wear.
(d) Inspect insulation for security of attachment and for condition.
(4) Repair.
( a ) Replace d e f e c t i v e c o v e r s a n d p a n e l s .
fasteners. (See figure 3-4).
( b ) Replace d e f e c t i v e
( c ) Replace d e f e c t i v e gaskets. New gaskets are installed by removing
t h e strip from the gasket a d h e s i v e backing and pressing the gasket in place.
( d ) Glue loose or new insulation to the panels with adhesive.
( 5 ) I n s t a l l a t i o n . Refer to figure 3-13 and install covers and panels by
t u r n i n g fasteners (9) one-quarter turn clockwise.
b. Condenser Coil and Tubes.
WARNING
W h e n using repressed a i r f o r b l o w i n g a n d c l e a n i n g , a i r
h o s e pressure must not exceed 30 psig, and individuals
m u s t wear eye protection equipment.
O r g a n i z a t i o n a l maintenance of the condenser coil and tubes is limited to in-
s p e c t i o n for damage and cleaning the coil. C l e a n outside area of coil with water and
dry with low pressure repressed air.
COMPRESSOR SECTION.
3-13.
a. Covers, Panels and Frame.
( 1 ) Removal. Remove the covers and panels by turning the fasteners (14,
figure 3-14) one-quarter turn counterclockwise.
( 2 ) C l e a n i n g . C l e a n all parts with a damp cloth and dry thoroughly.
(3) Inspection.
( a ) I n s p e c t c o v e r s and panels for dents and other damage.
(b) Inspect fasteners and receptacles for security of attachment.