Inspection.
I n s p e c t the evaporator coil assembly for damage which would
b.
impair serviceability.
c.
Removal.
( 1 ) Refer to figure 3-5 and remove end panels, f r o n t p a n e l a n d a i r f i l t e r
f r o m the evaporator coil section by turning fasteners (4) one~quarter turn counter-
clockwise.
(2) Pump dowm the refrigerant system in accordance with paragraph 4-6
and close shutoff valves at both ends of the evaporator coil.
(3) Loosen flare nuts on liquid and suction lines.
( 4 ) Unbolt f rent support (23, 31, f i g u r e 4 - 6 ) a n d r e a r s u p p o r t s ( 1 4 , 2 9 ) .
( 5 ) L i f t e v a p o r a t o r c o i l a s s e m b l y fromn frame.
d .  Replace.
R e f e r to figure 4-5 and r e p a i r o r r e p l a c e e v a p o r a t o r c o i l
c o m p o n e n t s as required.
Installation.
e.
( 1 ) P l a c e e v a p o r a t o r c o i l a s s e m b l y i n p o s i t i o n i n frame.
( 2 ) Place f rent supports (23, 31, figure 4-6) and r e a r supports (14, 29)
a n d bolt them to the evaporator coil assembly and to frame.
(3) Reconnect flare nuts at liquid and suction lines.
( 4 ) Purge opened refrigerant system of air in accordance with paragraph
4 - 9 and open shutoff valves.
(5) Refer to figure 3-5 and replace air filter and panels.
FILTER DRIER.
4-13.
a .  General,
The filter drier (12, figure 4-7) is located in the condenser
f a n section of the air conditioner. It is in the refrigerant liquid line to remove
a n d retain any foreign substance in the refrigerant. The filter drier should not be
r e p l a c e d with equipment of lesser capacity than the original equipment. Install a
n e w filter drier whenever the refrigerant system has been opened.
Removal.
b.
( 1 ) Refer to figure 3-7 and remove panels from the c o n d e n s e r f a n s e c t i o n
b y turning fasteners (8) one-quarter turn counterclockwise and r e m o v i n g screws (22)
and washers (23).
( 2 ) Pump down the refrigerant system in accordance w i t h paragraph 4-6
and close liquid line shutoff valve.
( 3 ) Disconnect tubes from top and bottom of filter d r i e r ( 1 2 , f i g u r e
4-7) by loosening flare nuts (1),