TM 5-4120-369-14
CONTROL MODULE COMPONENTS - Continued.
4-28.
(b.) Removal.
(1) Remove control module per paragraph 4-27
(2) Remove pin from circuit breaker.
(3) Remove 4 screws.
(4) Remove wires from circuit breaker.
(5) Remove circuit breaker,
(c) Installation.
(1) Install the compressor circuit breaker, reconnect the wires, secure
circuit breaker with 4 screws.
(2) Replace pin.
(3) Install the control module per paragraph 4-27.
(2) Mode Selector Switch (Rotary). (S-1)
Check for loose connections, loose control knob and cracked or
(a) Testing
broken casing. Check for continuity with a mulimeter.
If no continuity exists with switch in either one of the four "ON" positions or if the casing is
broken or cracked, replace the mode selector switch. If knob is loose, tighten set screw. If
knob is defective, replace.
(b) Removal,
(1) Remove control module per paragraph 4-27
(2) Remove knob from switch.
(3) Remove 3 screws
(4) Remove wires from switch,
(5) Remove switch.
(c) Installation.
(1) Install the mode selector switch, reconnect the wires, secure switch
with 3 screws.
(2) Replace knob.
(3) Install the control module per paragraph 4-27.
4-24
|