|
|
TM 5-4120-369-14
5-27.
FLUID PRESSURE REGULATOR VALVES - Continued
(1) Refer to paragraph 6-3 and discharge the refrigerant system.
(2) Refer to paragraph 4-18 and remove the air conditioner top rear cover.
(3) Refer to figure 5-11 and unclamp the regulator valve sensing bulb.
(4) Remove the regulator valve mounting clamp.
(5) Unsolder the regulator valve from the refrigerant system tubing. Remove by
drawing the bulb through the compartment wall.
Installation.
c.
(1) Refer to figure 5-11 and mount the fluid pressure regulator against the compart-
ment wall using the mounting clamp.
Brazing operations should be carried out using approved
eye protection equipment and rods not containing cadmium.
Certain brazing operations may require mechanical ventilation.
Local preventive medicine personnel should be queried if
doubt exists as to rod composition or ventilation requirements.
(2)
Solder the pressure regulator valve to the refrigerant system tubing.
(3)
Feed the sensing bulb through the compartment wall and clamp in place.
(4)
Refer to paragraph 6-3 and leak test the refrigeration system.
(5)
Refer to paragraph 6-3 and purge the refrigeration system.
(6)
Refer to paragraph 4-18 and install the top covers.
Caution should be exercised with fluorocarbon refrigerant
gas (freons) as they can displace oxygen and thereby
cause suffocation.
Personnel with a history or other evidence of cardiac
rhythm abnormalities should be made aware of the potential
for aggravation of existing cardiac rhythm abnormalities
or the induction of arrythmias, as a result of exposure
to fluorocarbon refrigerant gases (freons). Such indivi-
uals should be evaluated by local medical authorities before
working in environments where potential freon exposure
may occur.
(7)
Refer to paragraph 6-3 and charge the refrigerant system.
5-30
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |