TM 5-4120-374-13
W-Weekly
Q-Quarterly
Interval
Item
Procedures: Check for and Have Repaired or
No.
W
Q
Item to be Inspected
Adjusted as Necessary
q
a. Remove twelve (12) screws securing air filter cover to
1
Air Filter
bottom of air conditioner. Remove air filter cover and
gasket.
b. Slide air filter down and out of air conditioner.
Dry cleaning solvent, P-D-680 or P-S-661, used to clean parts is potentially
dangerous to personnel and property. Avoid repeated and prolonged skin contact.
Do not use near open flame or excessive heat. Flash point of solvent is 100F (38C).
c. Clean air filter with P-D-680 pr P-S-661 dry cleaning solvent
or warm soapy water and dry with low pressure compressed
air.
d. Inspect air filter for damaged or clogged condition. Replace
air filter if damage is indicated.
e. Inspect two (2) rubber pads on bottom of air filter for
damage. Replace pads if damage is indicated. Secure pads
with adhesive per specification MMM-A-121.
f. Dip or spray air filter with filter-kote or oil per specifica-
tion MlL-L-2104 Grade 20, 30 or better. Drain off excessive
oil before installation.
g. Slide air filter up into air conditioner.
h. Install gasket and air filter cover and secure with twelve
(12) screws.
4-6
|