TM
5-4120-374-13
LOCATION/lTEM
ACTION
R
E
M
A
R
K
S
RIGHT
SIDE
OF
HOUSING
Death or serious injury may occur if capacitor is not discharged prior to removal.
Disconnect input power source before performing this maintenance task.
a . Discharge motor capacitor.
9.
Fan
Motor
b . Remove upper four (4) capscrews and self-locking nuts securing
motor to motor mounting bracket.
c
. Slide motor back against bulkhead.
d
. Loosen setscrew in hub of condenser fan.
. Remove condenser fan.
e
f . Tag and disconnect electrical leads to motor capacitor.
g
. Tag and disconnect leads to fan motor.
h
. Remove fan motor from housing.
4-29
|