REMARKS
ACTION
LOCATION/lTEM
RIGHT SIDE OF HOUSING
3 . M o t o r C a p a c i t o r a . Test motor capacitor with a suitable capacitor tester for
continuity, leakage short, and capacitance.
b . The motor capacitor is rated at 3 microfarads, 370 volts.
c . Replace motor capacitor if testing indicates that it is
defective.
4 . M o t o r C a p a c i t o r a . Install motor capacitor in capacitor bracket.
b. Align holes in capacitor bracket and motor.
c. Secure capacitor bracket with two (2) screws.
d. Connect electrical leads to motor capacitor and remove tags.
e . Cover electrical leads with rubber boot.
a . Align holes in right side panel with holes in housing.
5. Right Side Panel
b . Secure right side panel with seventeen (17) screws.